Greenhouse heater size in Btu per hour equals covering area in sq ft times the U-value times the temperature rise you want. A 450 sq ft house with double polycarbonate, held 40°F above the outside low, needs about 10,800 Btu per hour.
The formula
University of Alaska Fairbanks Extension gives the heat loss formula as surface area of the covering times the heat loss factor times the temperature difference between the highest inside and lowest outside temperature. Written out: Btu/h = SA x U x TD. Count walls and roof, not the floor. TD is the inside temperature you want minus the coldest night you expect (check your NOAA forecast office).
| Covering | U (Btu/h per sq ft per °F) |
|---|---|
| Single glass or single polycarbonate | 1.2 |
| Single plastic film | 1.25 |
| Double plastic film | 0.8 |
| Double acrylic or polycarbonate | 0.6 |
| Double film with thermal blanket | 0.4 |
Source: Table 1 in the Alaska Extension publication above. Higher U means less insulation.
Worked example
Say the covering totals 450 sq ft, you want 50°F inside, and the coldest night is 10°F, so TD = 40.
| Covering | Calculation | Btu/h | Watts (Btu/h / 3.412) |
|---|---|---|---|
| Single polycarbonate | 450 x 1.2 x 40 | 21,600 | 6,331 |
| Double film | 450 x 0.8 x 40 | 14,400 | 4,220 |
| Double polycarbonate | 450 x 0.6 x 40 | 10,800 | 3,165 |
| Double film plus blanket | 450 x 0.4 x 40 | 7,200 | 2,110 |
Sizing to the number is the starting point. Drafts around doors and vents add loss that the table does not capture, so in our judgment some headroom above the calculated number is sensible; how much is your call, since the source gives no margin figure. Lowering the target helps too: each degree you drop from TD = 40 trims the load by 1/40, or 2.5%. A frost-tolerant crop kept at 40°F needs 450 x 0.6 x 30 = 8,100 Btu/h instead of 10,800.
Pick the heater type
Electric. One watt gives 3.412 Btu per hour, so a 1,500 W unit supplies about 5,100 Btu/h. The 10,800 Btu/h house needs more than two such units (10,800 / 5,118 = 2.1), which is a wiring question, not a shopping one. Do not stack heaters on one circuit. The CPSC says to plug a space heater directly into a wall outlet, never an extension cord or power strip, and never to leave it on unattended or while you sleep. If you need a new outdoor circuit, have a licensed electrician size and install it, and use only heaters the maker rates for greenhouse or damp locations. A household space heater built for a dry living room does not belong in a humid greenhouse.
Propane or other fuel. Fuel heaters produce carbon monoxide (CO). The Alaska source says oil, kerosene, white gas, and diesel heaters are not recommended unless adequate ventilation is provided. Check the manual for the rated Btu/h, required fresh-air opening, clearances, and whether the model is approved for greenhouse use, and ventilate exactly as it specifies. Never leave a fuel heater running unattended or while you sleep, and add a battery CO alarm. The CPSC space heater checklist (October 2011) warns that unvented heaters need a constant supply of fresh air to operate safely.
Common mistakes
- Sizing from floor area instead of covering area.
- Using the average winter low instead of the coldest night.
- Skipping a thermostat, so the heater runs at full output on sunny afternoons.
- Buying a bigger heater when a second glazing layer would cut the load for less.
Ready to shop? See our ranked best greenhouse heaters. For a full walkthrough with a gable house, read how to heat a greenhouse in winter; to lower the load first, see polycarbonate thickness or heat-free options in heating without electricity. We research and compare; we do not run our own product trials. See How We Choose.