To refill a fully drained 12 V 100 Ah LiFePO4 battery in one sunny day, plan on about 350 W of solar panels, which in practice means two 200 W panels or one 400 W panel feeding an MPPT charge controller: 12.8 V x 100 Ah = 1,280 Wh, and 1,280 Wh / (5 peak sun hours x 0.75 real-world derate) = about 341 W.

Most days you will not start from empty, so the panel count you actually need depends on how much you drain overnight and how much sun your roof or yard gets in the season you care about. The table and examples below cover both.

The Formula

Panel watts needed = watt-hours to replace / (peak sun hours x 0.75 derate).

  • Watt-hours to replace: battery voltage x amp-hours x the share you drained. A LiFePO4 “12 V” battery is four 3.2 V cells in series, so use 12.8 V, not 12 V. A full 100 Ah battery holds 12.8 x 100 = 1,280 Wh.
  • Peak sun hours: the number of hours of full-strength sun your site gets in a day. Five is a common planning figure for a clear day in much of the U.S. in spring and summer; winter is lower. The PVWatts calculator from the National Laboratory of the Rockies (formerly NREL) gives a figure for your ZIP code.
  • 0.75 derate: a common planning figure for heat, panel angle, dust, wiring, and controller losses. Panels rarely deliver their label rating outside a lab.

Panel Watts by Sun Hours and Depth of Discharge

Each cell below is the Wh to replace / (sun hours x 0.75), rounded to the nearest watt. Round up to the next panel combination you can buy.

Peak sun hoursFull recharge (1,280 Wh)Half recharge (640 Wh)Practical panel setup for a full recharge
3 (short winter day)about 569 Wabout 284 WThree 200 W panels
4about 427 Wabout 213 WTwo 200 W panels plus a 100 W panel, or 450 W to 480 W
5 (common planning figure)about 341 Wabout 171 WTwo 200 W panels, or one 400 W
6 (long, clear summer day)about 284 Wabout 142 WOne 300 W panel, or two 200 W for margin

The half-recharge column is the more realistic one for daily use. If you only draw the battery down to 50 percent overnight, a single 200 W panel covers the refill on a five-hour day.

A Worked Example From Real Household Loads

Start with the load, not the panel. Say the battery runs a mesh router and a TV through a small inverter during an outage:

  • eero 6+ mesh router, rated by eero at 4.5 W: 4.5 W x 24 h = 108 Wh.
  • 55 in LG 55QNED85TU TV, ENERGY STAR on-mode power 76.9 W: 76.9 W x 5 h = about 385 Wh.
  • Total at the outlet: 108 + 385 = 493 Wh. Through a 0.85 efficient inverter, the battery supplies 493 / 0.85 = about 580 Wh.

To put 580 Wh back on a five-hour day: 580 / (5 x 0.75) = about 155 W, so one 200 W panel. On a three-hour winter day: 580 / (3 x 0.75) = about 258 W, so two 200 W panels. The battery itself has room to spare, since 580 Wh is less than half of its 1,280 Wh.

For the folding-panel route, a pair of 200 W portable panels such as the Renogy 200W Portable Solar Panel covers the five-hour case. Check that the panel’s output lead ends in MC4 connectors, or comes with an adapter, so it fits a standalone charge controller rather than only a power station.

Size the Charge Controller, Too

Panels cannot connect straight to a bare 12 V battery; a charge controller sits between them and limits voltage and current. Its size follows the panel watts: controller amps = panel watts / charging voltage.

  • 400 W of panels: 400 W / 14.4 V = about 28 A. Victron rates its SmartSolar MPPT 100/30 at 30 A, with a nominal 440 W of panels on a 12 V battery and a 100 V maximum open-circuit voltage.
  • 600 W of panels: 600 W / 14.4 V = about 42 A, which needs a 50 A class controller. Victron lists its MPPT 100/50 at 50 A and 700 W on 12 V.
  • Battery limit: the battery’s own BMS (battery management system) caps charge current. Battle Born recommends 0.5C and lists 50 A as the maximum charge current for its 100 Ah 12 V battery, so 42 A is inside the limit. Other brands differ; read your battery’s manual.

Pick MPPT (maximum power point tracking) over PWM for this job. Victron states its MPPT controllers can harvest up to 30 percent more energy than PWM controllers, mostly under changing cloud cover. Set the controller to the battery maker’s lithium profile; Battle Born lists absorption at 14.2 to 14.6 V and float at 13.4 to 13.8 V.

Series or Parallel for Two Panels

Panel voltages add in series and currents add in parallel. Renogy lists the 200W Portable panel above at 21.6 V open-circuit voltage (Voc), so two in series reach 2 x 21.6 V = 43.2 V, under the 100 V limit of the Victron controllers above. Victron also notes the panel voltage must exceed battery voltage plus 5 V before the controller starts charging, which series wiring clears early in the morning. Voc rises on cold mornings, so leave margin under the controller’s limit; your panel and controller manuals list both numbers.

Common Mistakes

  • Using the label watts with no derate. 1,280 Wh / 5 h = 256 W looks like enough, but after the 0.75 derate a 256 W array only delivers about 960 Wh on that day.
  • Sizing for summer when outages hit in winter. Look up your winter sun hours before you buy.
  • Ignoring the cold-charge cutoff. Battle Born’s charge range starts at 32°F on its standard model; below that, the BMS refuses solar input no matter how many panels you have.
  • Undersized controller. A 20 A controller on 400 W of panels clips the output at about 20 A x 14.4 V = 288 W.

If wiring a battery, controller, and inverter is more than you want to take on, a portable power station has all three in one box; see how many watts of solar charge a power station. For what the BMS inside the battery does, see what a battery management system is, and for controller basics, MPPT charge controllers explained. Our ranked panel picks are in the best solar panels for power stations.