For a 1/2 HP submersible well pump, plan on a generator of at least 2 kW (2,000 W) if the pump has a 3-wire motor with a separate control box, or 3 kW for a 2-wire motor; a 1 HP pump needs at least 4 kW or 6 kW. Those are Franklin Electric’s minimum generator ratings for its submersible motors, before you add anything else in the house.

Then check voltage. Larger submersible pumps typically run on 230 to 240 V, and a generator with only 120 V outlets cannot run them no matter how many watts it makes. Both checks come before you look at brands.

Minimum Generator Size by Pump Horsepower

The table below comes from the generator section of Franklin Electric’s 2026 AIM (Application, Installation, Maintenance) manual for submersible systems. The ratings already account for the motor’s starting draw, which is why they sit well above the motor’s own kilowatt figure.

Motor HPMotor kWMinimum generator, 3-wire motorMinimum generator, 2-wire motor
1/30.251.5 kW2.25 kW
1/20.372 kW3 kW
3/40.553 kW4.5 kW
10.754 kW6 kW
1.51.15 kW7.5 kW
21.57.5 kWnot listed

A 2-wire motor has its starting components inside the motor down the well, while a 3-wire motor uses a control box mounted above ground, usually near the pressure tank. If you see a separate control box wired between the pressure switch and the well, you likely have a 3-wire pump; the pump’s paperwork or the control box label confirms horsepower and voltage.

Why the Starting Number Is So Large

A pump motor draws several times its running power for the moment it spins up a column of water. Champion’s generator wattage chart lists a 1/2 HP well pump at 750 to 1,000 running watts and 1,500 to 2,000 starting watts, and a 1 HP pump at 1,000 to 2,000 running and 2,000 to 4,000 starting. The Eugene Water and Electric Board (EWEB) chart lists a 1/3 HP well pump at 1,000 running watts plus 2,000 additional starting watts, a 3,000 W peak.

Franklin also states the requirement in voltage terms: a generator must deliver at least 65 percent of the motor’s rated nameplate voltage during starting to give the motor enough torque. An undersized generator sags below that, and the motor may not develop enough torque to start. More on the two kinds of watts is in running watts vs starting watts.

Example: Pump Plus Fridge Plus Furnace Fan

Start with the load. A rural home with a 1/3 HP well pump wants the pump, a refrigerator, and a furnace fan during a winter outage. Using EWEB’s chart, where starting watts are added on top of running watts:

  • Running total: well pump 1,000 W + refrigerator 700 W + 1/3 HP furnace fan 700 W = 2,400 W.
  • Largest single starting add: the refrigerator at 2,200 W (the pump adds 2,000 W, the fan 1,400 W).
  • Peak to plan for: 2,400 W + 2,200 W = 4,600 W, assuming only one motor starts at a time.

So a generator rated about 5,000 W running covers this house with some margin. Swap in a 1 HP 2-wire pump and the more conservative method is to reserve Franklin’s 6 kW minimum for the pump and add the other running loads: 6,000 W + 700 W + 700 W = 7,400 W. A full worksheet for the rest of the house is in what size generator you need for your house.

The 240 V Question

In Franklin’s 4-inch single-phase motor line, 1/2 HP motors come in 115 V and 230 V versions, while 3/4 HP and larger motors are 230 V only; the nameplate or control box label tells you which you have. A generator reaches a 240 V pump only through a 240 V outlet such as an L14-30R or 14-50R, and that outlet feeds the house through a transfer switch or similar equipment. Compare two generators: the WEN DF480iX has 4,000 W running and no 240 V outlet, so it cannot run a 240 V pump at all, while the Westinghouse iGen12000DFc lists 9,000 running watts on gasoline with L14-30R and 14-50R outlets, enough for the 7,400 W example above.

A well pump is hard-wired, so the connection is not a plug-in job. Franklin’s manual states that transfer switches must be used any time a generator backs up a home on utility power lines, and it says to contact the power company. Have a licensed electrician choose and install the transfer equipment and pull any permit; the concepts are explained in transfer switch basics.

Running the Pump on a Generator

  • Start the generator first. Franklin says to start the generator before turning on the motor and to turn the motor off before shutting the generator down.
  • Do not let it run out of fuel with the pump on. Franklin warns that the motor’s thrust bearing can be damaged if the generator coasts down or runs dry with the motor running.
  • Watch frequency. Pump speed follows generator frequency; Franklin notes that running 1 to 2 Hz low can keep the pump below its performance curve, and 1 to 2 Hz high can trip overloads.
  • Derate at altitude or on natural gas. Franklin points to the generator maker’s derating guidance; dual fuel models also list lower output on propane than on gasoline, so size from the propane figure if that is the fuel you will use.

Carbon Monoxide Comes With the Generator

Every gas, propane, or dual fuel generator makes carbon monoxide. The CPSC says to run portable generators outdoors only, at least 20 ft from the home, far from windows, doors, and vents, with the exhaust pointed away from the home, never in a garage, basement, or shed, and to keep CO alarms on every level of the home and outside sleeping areas. An enclosed pump house is no better a place for it than a shed. The CPSC estimates about 100 people in the US die each year from CO linked to portable generators. Follow the manufacturer’s instructions and local rules; the full checklist is in how to run a generator safely.

Common Mistakes

  • Sizing from the running watts alone. A 1/2 HP pump that runs on 1,000 W can still need a 2 to 3 kW generator to start.
  • Buying a 120 V only generator for a 240 V pump. Check the pump’s voltage before you shop.
  • Starting the pump and the fridge together. Let one motor reach speed before the next one starts.
  • Adding a reduced voltage starter to a minimum-size generator. Franklin warns that the combination can damage the motor through low voltage.

Generators that meet these numbers, with their 240 V outlets and CO shutoff features listed, are compared in the best inverter generators for home use.

FAQ

How many watts does it take to start a well pump?

Champion lists 1,500 to 2,000 starting watts for a 1/2 HP pump and 2,000 to 4,000 for a 1 HP pump, as extra power on top of the running watts. Franklin’s generator minimums, which build in the start, run from 2 kW to 6 kW for those sizes depending on motor type.

Can a 3,500 W generator run a well pump?

It can meet Franklin’s minimum for a 1/2 HP 2-wire pump (3 kW) or a 3/4 HP 3-wire pump (3 kW), if it also supplies the pump’s voltage. It leaves little room for other loads during the start.

Can a portable power station run a well pump instead?

Only a unit that matches the pump’s voltage (240 V for most larger pumps) and has enough surge, connected through proper transfer equipment by a licensed electrician. Most 120 V stations cannot; options are covered in the best power stations for a well pump.