Use an automatic charger sized for the battery and run it from the generator, outdoors. Do not wire the generator straight to the battery. The charger converts generator AC into the voltage curve the battery needs, and it is the part that decides how fast and how safely the job goes.
Carbon monoxide first. Per the CPSC, portable generators go outdoors only, at least 20 ft from the home with the exhaust pointed away from any building, never in a garage, basement, or shed, and opening doors does not make that safe. Keep battery-operated or battery-backup CO alarms on every level and outside sleeping areas. Roughly 100 people a year in the US die of CO from portable generators.
Step by Step
- Match the charger to the chemistry. Battle Born lists absorption at 14.2 to 14.6 V and 0.5C recommended for its LiFePO4 batteries. Discover Battery says the charger’s curve must meet the battery’s requirement.
- Set up the generator outdoors, off, and put the charger and battery in a ventilated spot. Discover Battery warns that charging flooded lead-acid batteries can produce an explosive mixture of hydrogen and oxygen.
- Connect the charger to the battery with the charger unplugged. Discover Battery says to turn the charger off before removing leads, to avoid sparks.
- Start the generator, then plug in the charger through an outdoor-rated cord whose rating exceeds the load, as the CPSC advises.
- If the battery gets hot or gasses violently, Discover says to reduce the rate or halt the charger.
Size the Generator and the Time
Take a 100 Ah, 12 V battery that is 50% down, charged by a 20 A charger at about 14.4 V with an assumed 0.85 charger efficiency. The 0.85 and the 1.2 below are planning assumptions, not measured values:
- AC draw: 20 A x 14.4 V / 0.85 = about 340 W.
- Time: 50 Ah x 1.2 (assumed allowance for charging losses) / 20 A = about 3 hours.
- Fuel: Honda lists the EU2200i at 0.95 gal for 8.1 hours at 1/4 load, about 0.12 gal an hour. Three hours is about 0.35 gal or less.
Any inverter generator covers 340 W, but it spends fuel on a small load. If you also run a fridge or sump pump, add their running watts, as in what size generator you need and running vs starting watts. An inverter generator also gives steadier output for sensitive chargers.
Keep the battery out of the exhaust path and the generator downwind of the work area. Refuel only with the engine off and cool, per the generator manual. When the charger switches to its float or finish stage, the AC draw falls well below the 340 W peak, so an inverter generator with an economy mode can idle down and the last hour should cost less fuel. Stop once the charger reports done, and for a lead-acid battery a resting voltage near 12.65 V or higher (Discover Battery’s 100% reading) suggests it is full.
Do Not Backfeed
The CPSC says never to power house wiring by plugging a generator into a wall outlet. It risks electrocuting utility workers and neighbors on the same transformer. If you want the generator tied to the house, see transfer switch basics and hire a licensed electrician.
Related: how to run a generator safely and LiFePO4 vs lead-acid.