The blower in a typical gas furnace draws roughly 400 to 600 W while it runs, and generator sizing charts plan for about 800 running watts plus 2,350 additional starting watts for a 1/2 HP blower to leave headroom. In a U.S. Department of Energy (DOE) Building America field study, swapping older PSC blower motors for brushless ones cut heating-mode draw by 126 W, or 23 percent, which works out to about 550 W before the swap and about 420 W after.
The blower is only part of the electrical load. A gas furnace also has a short ignition stage and a small draft inducer, and they do not all peak at once. Separating those stages is what keeps you from buying a generator or battery that is too small, or far too large.
Blower vs Ignition: Two Different Loads
| Part | When it draws power | Typical figure | Source |
|---|---|---|---|
| Blower, older PSC motor | Whenever heat is moving through the ducts | about 550 W in heating mode (derived below) | DOE Building America case study, 2014 |
| Blower, brushless ECM or BPM motor | Same, at variable speed | about 420 W in the same homes (derived below) | DOE Building America case study, 2014 |
| Blower, planning figure for 1/2 HP | Running / extra at start | 800 W running, plus 2,350 W more at start | Briggs and Stratton generator wattage chart |
| Hot surface igniter, silicon carbide 120 V | Seconds at the start of each heating cycle | 3.5 to 5 A rated at 132 V | Supco replacement igniter listings |
| Draft inducer | Before ignition and while burners run | a smaller motor than the blower; check your rating plate | furnace rating plate |
The DOE figures come from a study in Syracuse, New York, that replaced PSC (permanent split capacitor) blower motors with brushless permanent magnet (BPM) motors. The replacements used 126 W less, a 23 percent cut, in heating mode. Working back: 126 W / 0.23 = about 548 W for the original motors, and 548 W minus 126 W = about 422 W for the replacements.
A second way to estimate uses airflow. A Building Science Corporation article on Building America research notes that simulation software assigns PSC blowers 0.5 W per cubic foot per minute (cfm), the same as the median from a California field survey of furnaces, so a furnace moving 1,000 cfm draws about 1,000 x 0.5 = 500 W, close to the field result.
The igniter is a brief spike, not a running load. A silicon carbide igniter rated up to 4 A works out to about 120 V x 4 A = 480 W, and Supco lists heat-up times under about 17 to 19 seconds. In the usual gas furnace sequence the inducer and igniter come on first and the blower follows after the burners light, so for sizing, the blower’s start is the moment that matters most.
Read Your Own Furnace’s Numbers
The furnace’s rating plate lists the blower motor’s horsepower and full load amps (FLA), the most current the motor is rated to draw. Multiplying by 120 V gives a ceiling, not an average. Comfort Aire’s 80 percent furnace spec sheet, for example, lists 8 FLA for 1/2 HP blowers and 14 FLA for 1 HP blowers:
- 1/2 HP: 120 V x 8 A = 960 W maximum.
- 1 HP: 120 V x 14 A = 1,680 W maximum.
Real draw at normal speed is usually well under the ceiling, which is why the DOE field average sits near 550 W. If you want the actual number, ask your HVAC technician to read the blower’s running amps with a clamp meter at the next service visit.
Generator Size for a Furnace: Worked Example
Start with the load. Take a house that wants the furnace, a full-size fridge, and a few lights on one portable generator, using planning-chart values so the margin is built in:
- Running watts: furnace blower 800 W + fridge about 235 W while the compressor runs (the top of the modern full-size range) + lights and router 100 W = 1,135 W.
- Largest single surge: Briggs and Stratton defines starting watts as the extra watts a motor needs to start, so the blower’s 2,350 W comes on top of everything already running for a moment: 1,135 W + 2,350 W = 3,485 W.
- Result: a generator rated at least 1,135 running watts and about 3,500 starting watts covers this house, and more starting headroom than that leaves room for the fridge and blower to start close together.
The method behind that peak calculation is laid out in running watts vs starting watts, and the whole-house version is in what size generator do I need.
Battery Runtime for a Furnace Blower
A battery power station also works for a furnace if the numbers fit. Assume the blower runs half of each hour on a cold night, a labeled example; your duty cycle depends on outdoor temperature and insulation. With the DOE’s PSC figure: 550 W x 0.5 = 275 W average. A 2,000 Wh station then lasts 2,000 Wh x 0.85 inverter efficiency / 275 W = about 6 hours. With a brushless blower at about 420 W: 420 x 0.5 = 210 W, and 1,700 Wh / 210 W = about 8 hours.
Power Quality and How the Furnace Gets Connected
Modern furnaces run on a control board that watches flame and power conditions, and HVAC technicians commonly report boards that misbehave on rough generator power. An inverter generator or power station with a clean sine wave lowers that risk; Champion, for example, rates its 2500W Dual Fuel Inverter at under 3 percent total harmonic distortion (THD). See pure sine wave inverters explained.
Most gas furnaces are hard-wired to their own circuit, so powering one from backup means a transfer switch or a similar arrangement. That is work for a licensed electrician, with your HVAC contractor confirming what the furnace needs; this page does not cover wiring steps. Transfer switch basics explains what the device does and why backfeeding through an outlet is dangerous.
Common Mistakes
- Sizing to the nameplate ceiling and the igniter spike as if both run all the time.
- Forgetting the blower’s starting surge, which is what trips an undersized generator.
- Assuming a gas furnace needs no electricity; without the blower, inducer, and controls it will not heat.
- Placing a generator near the furnace’s intake or exhaust vents; keep it outdoors at least 20 ft from the house, far from windows, doors, and vents, with the exhaust pointed away.
Any gas, propane, or dual fuel generator must run outdoors only, at least 20 ft from the home, far from windows, doors, and vents, with the exhaust pointed away from the home, never in a garage, basement, or shed, with battery-powered or battery-backup carbon monoxide (CO) alarms on every level and outside sleeping areas, per CPSC guidance, the manufacturer’s manual, and local rules. For equipment matched to this load, see our best backup power for a gas furnace, and for keeping the house warm if the furnace stays off, see how to keep a house warm without power.