Runtime in hours is amp-hours x 12 V x 0.8 / load watts. A 100 Ah, 12 V lithium battery feeding a 600 W load lasts 100 x 12 x 0.8 / 600 = 1.6 hours. The 0.8 is a planning factor, not a law, and it drops to about 0.43 for lead-acid, as the table below shows.
The Formula and Where 0.8 Comes From
Start with stored energy: amp-hours x volts = watt-hours (see what a watt-hour is). Then take only the part you can actually use: the share of the battery you allow yourself to drain, times the inverter’s efficiency. I use 0.85 for inverter losses as a planning allowance, not a measured spec; your inverter’s sheet gives the real figure.
| Battery type | Planned use of capacity | x Inverter efficiency (0.85) | Factor |
|---|---|---|---|
| LiFePO4 | Battle Born lists 100% depth of discharge; a planning allowance of 95 to 100% | 0.95 x 0.85 = about 0.8 | 0.8 |
| AGM or other sealed lead-acid | About 50%, the usual lead-acid rule of thumb (Victron rates a 110 Ah AGM at 600 cycles to 50%, 400 cycles to 80%) | 0.5 x 0.85 = about 0.43 | 0.43 |
Lead-acid ratings also assume a slow discharge. A heavy draw returns fewer amp-hours than the label, so treat lead-acid answers as best cases and read your battery’s datasheet.
Worked Example: A Fridge Overnight
Assume a fridge that draws 150 W while the compressor runs and runs about one-third of the time (read your own label or use a plug-in watt meter). Average load is 150 / 3 = 50 W, or 1,200 Wh a day.
- 100 Ah LiFePO4: 100 x 12 x 0.8 = 960 Wh. 960 / 50 = about 19 hours.
- 100 Ah AGM: 100 x 12 x 0.43 = 516 Wh. 516 / 50 = about 10 hours.
Compressor start-up surge matters too: the inverter must handle the starting watts, which our page on running watts vs starting watts explains. For a multi-day budget, use how many amp-hours you need for boondocking.
Worked Example: How Many Amp-Hours for a 2000 Watt Inverter?
Rearrange the formula: amp-hours = watts x hours / (12 V x 0.8). For one hour at the full 2,000 W: 2,000 / (12 x 0.8) = about 208 Ah of LiFePO4. For AGM, 2,000 / (12 x 0.43) = about 388 Ah.
The current is the second problem. At full load the battery supplies 2,000 / (12 x 0.85) = about 196 A. Battle Born’s BB10012i manual rates its battery management system at 100 A continuous (200 A for 30 seconds), so one 100 Ah battery cannot carry that load. Two in parallel would each sit near the limit. A 2,000 W inverter on 12 V is a heavy-current setup; a 24 V bank halves the current for the same watts.
Mistakes That Cut Runtime
- Using a starting (cranking) battery. It is built for short bursts, not deep discharge; see LiFePO4 vs lead-acid for what suits repeated draining.
- Forgetting the inverter’s own idle draw, which runs even with nothing plugged in. Look for the no-load figure in the inverter manual.
- Sizing from the label amp-hours of an old or cold battery. Age and low temperature both shrink capacity.
- Assuming every inverter is as efficient as the 0.85 allowance. Losses vary by model and load, and waveform type matters too; see pure sine wave inverters explained.
Wiring and Safety
Currents this high heat undersized cable. Use the cable gauge, fuse size and mounting the inverter and battery manuals specify, and have a licensed electrician handle any permanent installation in a house or RV. Flooded lead-acid vents hydrogen while charging, and sealed types can gas if overcharged, so follow the battery and charger manuals on ventilation. Mixing battery types in one bank is prohibited by Battle Born’s manual.